Pump Selection

 

Click on the type of product to see our comprehensive comparison chart.
  • Sump Pumps - Generally referred to as drainage or clear water sump pumps.  Most dewatering pumps have screens which prevent the solids from entering the pump.  These pumps are used to pump ground water out to grade or to a storm sewer.

  • Effluent Pumps - Effluent pumps are rated for use in sanitary sump drainage applications or clear water applications where higher gpm output is required.  When pumping grey water, pumps must be capable of passing limited amounts of 1/2” or 3/4“ solids.

  • Sewage Pumps - Sewage pumps are used in sanitary pumping applications where toilets are being used.  These pumps are capable of passing 2" solids.  Sewage pumps can also be used in clear water applications where higher gpm output is required.

  • Grinder Pumps - Grinder pumps are sewage handling pumps that actually, chop, grind and shred the sewage and reduce it to a slurry.  Sewage grinder pumps are capable of pumping this slurry through  smaller diameter pipe, as small as 1-1/4” and for much higher and longer distances than sewage handling pumps.

  • Cutter Pumps - Cutter pumps are very powerful sewage handling pumps that cut and  pass the solid.  Utilizing a Tungsten Carbide tipped impeller and a High Chrome Iron Cutter Plate, cutter pumps will solve the most demanding sewage and wastewater applications. As the solids pass through the cutter plate, they are cut into pieces and the deep vane impeller passes them along.

  • Battery-Operated Pumps - Emergency back-up pumps for taking over during power or primary pump failure.

  • Hi-Temp and Utility Pumps - High temp pumps are used for pumping liquid/effluent with temperatures up to 200 degree Fahrenheit.

  • Sink Tray Units - These units sit on the floor or under cabinets, no need to dig a sump.  And are used for removing water/effluent from laundry sinks, bar sinks, laundry sinks, utility sinks, dehumidifiers and condensate.  Units are pre-assembled and ready to install.

 

SUMP PUMPS

                    

Generally referred to as drainage or clear water sump pumps.  Most dewatering pumps have screens which prevent the solids from entering the pump.  These pumps are used to pump ground water out to grade or to a storm sewer.

Jim Murray
Model #
Manufacturer Manufacturer
Model #
Switch HP RPM Volt PH FLA Cord Discharge   Shut Off   TDH 5' 8' 10' 12' 15' 18' 20' 22' 25' 30' 32'
PJM-WFC-50 Jim Murray  PJM-WFC-50  Auto   1/2   1700   115   1   4.0   8'   1-1/4"     21'    GPM  50   44   40   34   26   13   6  -   -   -   - 
PJM-WFHD-PLUS Jim Murray  PJM-WFHD-PLUS  Auto   1/2   1700   115   1   4.0   8'   1-1/4"     21'    GPM  55   48  43   37   28  15   8  -   -   -   - 
PLG-6-CIA Little Giant  6-CIA  Auto   1/3   1550   115   1   9.0   10'   1-1/2"     18'    GPM  45   36   28   22   12   -   -   -   -   -   - 
PVL-PRO-33V     Little Giant  PRO-33V      Auto   1/3   1550  115  1   4.3   10'  1-1/2"     25'    GPM  50   45   41   37   31   22  16   -  -  -  -
PVL-ES-SFS Jim Murray  PVL-ES-SFS  Auto   1/3   1550   115   1   6.0   10'   1-1/2"     20'    GPM  50   44   42   38   27   12   -   -   -   -   - 
PVL-ES-AVF Jim Murray  PVL-ES-AVF  Auto   1/3   1550   115   1   6.0   10'   1-1/2"     20'    GPM  50   44  42   38   27   12   -   -   -   -   - 
PVL-ES-AFS Jim Murray  PVL-ES-AFS  Auto   1/3   1550   115   1   6.0   10'   1-1/2"     20'    GPM  50   44   42   38   27   12   -   -   -   -   - 
PVL-ES-MAN Jim Murray  PVL-ES-MAN  Manual   1/3   1550   115   1   6.0   10'   1-1/2"     20'    GPM  50   44   42   38   27   12   -   -   -   -   - 
PZM-EP-33M Metropolitan  BA-33M  Manual   1/3   3600   115   1   4.5   10'   1-1/2"     25'    GPM  60   53   52   48   40   28   22   -   -   -   - 
PZM-EP-33V-SJ Metropolitan  BA-33V-SJ  Auto   1/3   3600   115   1   4.5   10'   1-1/2"     25'    GPM  60   53   52   48   40   28   22   -   -   -   - 
PZM-EP-33M-AVF Metropolitan  BA-33M-SPI  Auto   1/3   3600   115   1   4.5   10'   1-1/2"     25'    GPM  60   53   52   48  40   28   22   -   -   -   - 
PZM-SP33 Barnes  SP33  Manual   1/3   3450   115   1   5.8   10'   1-1/2"     30'    GPM  50   44   43   39   34   26   24   20   13   -   - 
PZM-SP33VF Barnes  SP33VF  Auto   1/3   3450   115   1   5.8   10'   1-1/2"     30'    GPM  50   44   43   39   34   26   24   20   13   -   - 
PZM-SP50 Barnes  SP50X  Manual   1/2   3450   115   1   6.8   20'   1-1/2"     30'    GPM  65   62   58   55   45   35   32   25   15   -   - 
PZM-SP50VF Barnes  SP50VFX  Auto   1/2   3450   115   1   6.8   20'   1-1/2"     30'    GPM  65   62   58   55   45   35   32   25   15   -   - 
PZM-EP-50M Metropolitan  BA-50M  Manual   1/2   3600   115   1   5.8   15'   1-1/2" or 2"     30'    GPM  80   74   70   68   55   45   40   32   20   -   - 
PZM-EP-50V-SJ Metropolitan  BA-50V-SJ  Auto   1/2   3600   115   1   5.8   15'   1-1/2" or 2"    30'    GPM  80   74   70   68   55   45   40   32   20   -   - 
PZM-EP-50M-AVF Metropolitan  BA-50M-SPI  Auto   1/2   3600   115   1   5.8   15'   1-1/2" or 2"    30'    GPM  80   74   70   68   55   45   40   32   20   -   - 
PZM-SP75 Barnes  SP75X  Manual   3/4   3450   115   1   9.8   20'   1-1/2"     33'    GPM  80   73   72   68   63   55   53   50   40   20   - 
PZM-SP75VF Barnes  SP75VF  Auto  3/4   3450    115  1  9.8   20' 1-1/2"     33'   GPM  80  73  72  68  63  55  53  50  40  20  -
PZM-EP-75M Metropolitan  BA-75M  Manual   3/4   3600   115   1   7.5   15'   1-1/2" or 2"    35'    GPM  92   88   84   80   72   60   55   50   38   20   - 
PZM-EP-75V-SJ Metropolitan  BA-75V-SJ  Auto   3/4   3600   115   1   7.5   15'   1-1/2" or 2"    35'    GPM  92   88   84   80   72   60   55   50   38   20   -
PZM-EP-75M-AVF Metropolitan  BA-75M-SPI  Auto   3/4   3600   115   1   7.5   15'   1-1/2" or 2"    35'    GPM  92   88   84   80   72   60   55   50   38   20   -
PGT-ST1033-DFC1  Glentronics  ST1033-DFC1   Auto

 1/3

 

115

1

3.8

10'

1-1/2" 

 

 31'

 

GPM

 

 

46

               
PGT-ST1033-MAN  Glentronics   ST1033

Manual

 1/3

 

115

1

3.8

10'

1-1/2" 

 

 31'

 

GPM

 

 

46

               
PGT-ST1050-DFC1  Glentronics  ST1050-DFC1   Auto   1/2    115  1  4.8   10'  2"     36'    GPM      61                
PGT-ST1050-MAN  Glentronics  ST1050   Manual   1/2     115   1  4.8   10'  2"     36'    GPM      61                 
PGT-S3033-DFC2  Glentronics   S3033-DFC2   Auto   1/3     115   1   4.0   20'   1-1/2"    30'   GPM      50                 
PGT-S3033-MAN  Glentronics  S3033  Manual   1/3     115  1   4.0   20'  1-1/2"     30'   GPM       50                
PGT-S5050-DFC2  Glentronics  S5050-DFC2  Auto   1/2     115   1  6.8  20'   2"    36'   GPM      83                 
PGT-S3100-DFC2  Glentronics  S3100-DFC2   Auto   1     115   1 11.5   20'   2"    52'    GPM       92                

 

EFFLUENT PUMPS

        

Effluent pumps are rated for use in sanitary sump drainage applications or clear water applications where higher gpm output is required.  When pumping grey water, pumps must be capable of passing limited amounts of 1/2” or 3/4“ solids.

Jim Murray
Model #
Manufacturer Manufacturer
Model #
Switch HP RPM Volt PH FLA Cord Discharge   Shut Off   TDH 5' 8' 10' 12' 15' 18' 20' 22' 25' 30' 32'
PVL-PRO-33V Little Giant  PRO-33V  Auto   1/3   1550   115  1  4.3   8"   1-1/2"     25'    GPM  50   45  41   37  31   22  16        
PVL-ES-SFS Jim Murray  PVL-ES-SFS  Auto   1/3   1550   115   1   6.0   10'   1-1/2"     20'    GPM  50   44   42   38   27   12   -   -   -   -   - 
PVL-ES-AVF Jim Murray  PVL-ES-AVF  Auto   1/3   1550   115   1   6.0   10'   1-1/2"     20'    GPM  50   44   42   38   27   12   -   -   -   -   - 
PVL-ES-AFS Jim Murray  PVL-ES-AFS  Auto   1/3   1550   115   1   6.0   10'   1-1/2"     20'    GPM  50   44   42   38   27   12   -   -   -   -   - 
PVL-ES-MAN Jim Murray  PVL-ES-MAN  Manual   1/3   1550   115   1   6.0   10'   1-1/2"     20'    GPM  50   44   42   38   27   12   -   -   -   -   - 
PLG-8E-CIM-A Little Giant  8E-CIA-RFS  Auto   1/3   1750   115   1   11.0   15'   1-1/2"     21'    GPM  52   47   45   41   33   21   9   -   -   -   - 
PLG-8E-CIM Little Giant  8E-CIM  Manual   1/3   1750   115   1   11.0   15'   1-1/2"     21'    GPM  52   47   45   41   33   21   9   -   -   -   - 
PLG-8E-CIM-230 Little Giant  8E-CIM-230  Manual   1/3   1750   230   1   6.0   12'   1-1/2"     21'    GPM  52   47   45   41   33   21   9   -   -   -   - 
PLG-9E-CIM-A Little Giant  9E-CIA-RFS  Auto   4/10   1750   115   1   12.3   15'   1-1/2"     23'    GPM  57   55   53   50   44   34   25   10   -   -   - 
PLG-9E-CIM Little Giant  9E-CIM  Manual   4/10   1750   115   1   12.3   15'   1-1/2"     23'    GPM  57   55   53   50   44   34   25   10   -   -   - 
PZM-EP-33M Metropolitan  BA-33M  Manual   1/3   3600   115   1   4.5   10'   1-1/2"     25'    GPM  60   53   52   48   40   28   22   -   -   -   - 
PZM-EP-33V-SJ Metropolitan  BA-33V-SJ  Auto   1/3   3600   115   1   4.5   10'   1-1/2"     25'    GPM  60   53   52   48   40   28   22   -   -   -   - 
PZM-EP-33M-AVF Metropolitan  BA-33M-SPI  Auto   1/3   3600   115   1   4.5   10'   1-1/2"     25'    GPM  60   53   52   48   40   28   22   -   -   -   - 
PZM-SP33 Barnes  SP33  Manual   1/3   3450   115   1   5.8   10'   1-1/2"     30'    GPM  50   44   43   39   34   26   24   20   13   -   - 
PZM-SP33VF Barnes  SP33VF  Auto   1/3   3450   115   1   5.8   10'   1-1/2"     30'    GPM  50   44   43   39   34   26   24   20   13   -   - 
PZM-SP50 Barnes  SP50X  Manual   1/2   3450   115   1   6.8   20'   1-1/2"     30'    GPM  65   62   58   55   45   35   32   25   15   -   - 
PZM-SP50VF Barnes  SP50VFX  Auto   1/2   3450   115   1   6.8   20'   1-1/2"     30'    GPM  65   62   58   55   45   35   32   25   15   -   - 
PZM-EP-50M Metropolitan  BA-50M  Manual   1/2   3600   115   1   5.8   15'   1-1/2"     30'    GPM  80   74   70   68   55   45   40   32   20   -   - 
PZM-EP-50V-SJ Metropolitan  BA-50V-SJ  Auto   1/2   3600   115   1   5.8   15'   1-1/2"     30    GPM  80   74   70   68   55   45   40   32   20   -   - 
PZM-EP-50M-AVF Metropolitan  BA-50M-SPI  Auto   1/2   3600   115   1   5.8   15'   1-1/2"     30'    GPM  80   74   70   68   55   45   40   32   20   -   - 
PLG-9EH-CIM-A Little Giant  9EH-CIM-A  Auto   4/10   1750   115   1   13.0   20'   1-1/2"     32'    GPM  71   69   68   64   60   52   49   40   30   10   - 
PLG-9EH-CIM Little Giant  9EH-CIM  Manual   4/10   1750   115   1   13.0   20'   1-1/2"     32'    GPM  71   69   68   64   60   52   49   40   30   10   - 
PZM-SP75 Barnes  SP75X  Manual   3/4   3450   115   1   9.8   20'   1-1/2"     33'    GPM  80   73   72   68   63   55   53   50   40   18   - 
PZM-SP75VF Barnes     SP75VF  Auto  3/4  3450  115  1  9.8  20'  1-1/2"    33'   GPM  80  73  72  68  63  55  53  50  40  18  -
PZM-EP-75M Metropolitan  BA-75M  Manual   3/4   3600   115   1   7.5   15'   1-1/2"     35'    GPM  92   88   84   80   72   60   55   50   38   20   - 
PZM-EP-75V-SJ Metropolitan  BA-75V-SJ  Auto   3/4   3600   115   1   7.5   15'   1-1/2"     35'    GPM  92   88   84   80   72   60   55   50   38   20   - 
PZM-EP-75M-AVF Metropolitan  BA-75M-SPI  Auto   3/4   3600   115   1   7.5   15'   1-1/2"     35'    GPM  92   88   84   80   72   60   55   50   38   20   - 
PLG-WS51M         Little Giant  WS51M  Manual   1/2  1750   115   1 11.6   20'   2"     27'    GPM 155 130 120  100   83   70   52  30  -    -  - 
PLG-WS50M-20  Little Giant  WS50M-20   Manual  1/2   3450   115   1  11.6   20'  2"     42'   GPM 100  95   92  85   80  70  64  55  50   42 38 
PLG-WS50M-12-2 Little Giant  WS50M-12-2  Manual   1/2   3450  208-230   1   9.7   20'  2"    42'   GPM 100  95  92  85  80  70  64  55   50  42 38 

 

SEWAGE PUMPS

                          

Sewage pumps are used in sanitary pumping applications where toilets are being used.  These pumps are capable of passing 2" solids.  Sewage pumps can also be used in clear water applications where higher gpm output is required. 

Jim Murray
Model #
Manufacturer Manufacturer
Model #
Switch HP RPM Volt PH FLA Cord Discharge   Shut Off   TDH 5' 8' 10' 12' 15' 18' 20' 22' 25' 30' 32'
PLG-9SN-CIM-A Little Giant  9SN-CIA-RF  Auto   4/10   1750   115   1   8.5   20'   2"     20'    GPM  110   85   78   55   30   -   -   -   -   -   - 
PLG-9SN-CIM Little Giant  9SN-CIM  Manual   4/10   1750   115   1   8.5  20'   2"     20'    GPM  110   85   78  55   30   -   -   -   -   -   - 
PLG-9SN-CIM-230 Little Giant  9S-CIM-230  Manual   4/10   1750   230   1   6.5   15'   2"     18'    GPM  110  85
 78
55
 30  -   -   -   -   -   - 
PLG-10SN-3IN Little Giant  10SN-CIM  Manual   1/2   1750   115   1   9.5   15'   3"     25'    GPM  120   105   95   85   70   40   30  -   -   -   - 
PZM-SEV412-A Barnes  SEV412A  Auto   1/2   3450   115   1   10.5   20'   2"     25'    GPM  70  70  70   65   55   42   34   24   -   -   - 
PZM-SEV412 Barnes  SEV412  Manual   1/2   3450   115   1   10.5   20'   2"     25'    GPM  70   70   70   65   55   42   34   24   -   -   - 
PZM-SE411 Barnes  SE411  Manual   4/10   1750   115   1   12.0   15'   2"     26'    GPM  116   102   95   86   70   44   38   28   -   -   - 
PZM-SE421 Barnes  SE421  Manual   4/10   1750   230   1   12.0   15'   2"     26'    GPM  116   102   95   86   70   44   38   28   -   -   - 
PLG-14S-CIM Little Giant  14S-CIM  Manual   1/2   1625   115   1   11.6   20'   2 or 3"     25'    GPM  130   114   100   84   68   48   38   18   -   -   - 
PLG-14S-CIM-208 Little Giant  14S-CIM-208  Manual   1/2   1625   208/240   1   4.6   20'   2 or 3"     25'    GPM  130   114   100   84   68   48   38   18   -   -   - 
PZM-SE51 Barnes  SE51  Manual   1/2   1750   115   1   11.6   20'   2 or 3"     26'    GPM  170   150   138   120   98   70   50   38   -   -   - 
PZM-3SEV514L
Barnes
3SEV514L  Manual
 1/2
 1750
 115
 1
 12.0
 15'
 2 or 3"
   27'
  GPM  -
 -  130
 120
 98
 70
 50  38 -
-
-
PZM-SE52 Barnes  SE52  Manual   1/2   1750   240   1   5.9   20'   2 or 3"     26'    GPM  170   150   138   120   98   70   50   38   -   -   - 
ZBUR-3SEV524L Barnes
3SEV524L  Manual
 1/2
 1750
 240
1
 6.3
15'
2 or 3"
   27'
  GPM
  -  -
 130
 120
 98
 70  50
 38
  -
  -
  -
PZM-3SE774L Barnes  3SE774L  Manual   3/4   1750   208-240   1   7.4/7.0   20'   2 or 3"     30'    GPM  181   162   158   140   125   95   87   75   40   -   - 
PZM-3SE1074L Barnes  3SE1074L  Manual   1   1750   200-240   1   8.8/8.3   20'   2 or 3"     37'    GPM  225   210   190   180   165   140   135   120   95   50   35 
PZM-3SEV1024L Barnes 3SEV1024L Manual
 1
 1750
 200-230
 1
 9.0/8.5
 15'
 2 or 3"
   37'
  GPM  -
  -  180  168
 150
 135
 125
 115
100
 68
 50
PLG-16S-CIM Little Giant  16S-CIM  Manual   1   1625   230   1   11.0   20'   2 or 3"     35'    GPM  180   168   158   148   128   110   100   88   70   38   - 
PLG-16S-CIM-208  Little Giant  16S-CIM-208   Manual   1   1625   208   1   11.0   20'  2 or 3"    35'    GPM   180   168   158   148   128   110   100   88  70  38   - 
PLG-WS102HM-12  Little Giant  WS102HM-12   Manual   1  3450  230   1   13.3  30'   2"    48'   GPM   -  190  170  148  130  124   100  74  45  -  -
PLG-16S-CIM-3PH  Little Giant  16S-CIM-3PH   Manual   1   1725  200/240/460   3 6.8/6.3/3.2   20'  2 or 3"     35'    GPM   180   168   158   148   128   110   100   88   70   38  - 
PZM-SKHS50M1  Hydromatic  SKHS50M1  Manual   1/2     115  1  14.2   20'   2 or 3"    45'    GPM   -    -    -    -  144     -  124 112   98  72  -
PLG-WS52HM  Little Giant   WS52HM   Manual   1/2   1750  115   1   11.6   30'   2"     29'    GPM  156  135   128   108   97   80   68  50  32  -   - 
PLG-WS52HM-12  Little Giant  WS52HM-12   Manual   1/2   3450   208-230   1   11.6  30'  2"    29'    GPM   156   135   128  108   97   80   68   50   32   -   - 
PZM-SKHS50M2  Hydromatic  SKHS50M2  Manual   1/2    230   1   8.3   20'  2 or 3"     45'    GPM    -    -    -    -  144     -  124  112   98   72  - 
PZM-SKHS100M2  Hydromatic  SKHS100M2   Manual   1     240   1   11.4   20'   2 or 3"     58'   GPM    -    -    -    -    -     -   146  138  126   104  - 
PLG-18S-CIM  Little Giant  18S-CIM   Manual   1-1/2  3000   230  1  15.5  20"   2 or 3"     64'    GPM    -     -  160    -    -    -   137    -    -   111   -
PZM-3SE594L Barnes  3SE594L  Manual   1/2   1750   200-240   3   3.2/3.0   15'   2 or 3"     26'    GPM  170   150   138   120   98   70   50   38   -   -   - 
PZM-3SE544L Barnes  3SE544L  Manual   1/2   1750   480   3   1.5   15'   2 or 3"     26'    GPM  170   150   138   120   98   70   50   38   -   -   - 
PZM-3SEV594L Barnes
3SEV594L  Manual
 1/2
 1750
 200-240
 3
 3.7/3.8
 15'
 2 or 3"
   26'
  GPM
 -
 -  130
 120
 100
 82
 68
 55  25
 -
 -
PZM-3SEV544L
Barnes
3SEV544L  Manual
 1/2
 1750
 480
 3
  1.9  15'
 2 or 3"
   26'   GPM
 -
  -  130
 120
 100
 82
 68  55
 25
 -
 -
PZM-3SE1094L Barnes  3SE1094L  Manual   1   1750   200-240   3   5.1/4.9   15'   2 or 3"     37'    GPM  225   210   190   180   165   140   135   120   95   50   35 
PZM-3SE1044L Barnes  3SE1044L  Manual   1   1750   480   3   2.4   15'   2 or 3"     37'    GPM  225   210   190   180   165   140   135   120   95   50   35 
PZM-3SEV1094L
Barnes
3SEV1094L  Manual
 1  1750
 200-240
 3  5.3/5.1
 15'  2 or 3"
   37'   GPM
 -  -  180
 168
 150
 135
 125  115
 100  68
 50
PZM-3SEV1044L Barnes
3SEV1044L  Manual
 1  1750
 480
 3
 2.5  15  2 pr 3"
   37'
  GPM  -
 -
 180
 168 1 50
 135
 125
 115
 100
 68  50

 

GRINDER PUMPS

                       

Grinder pumps are sewage handling pumps that actually, chop, grind and shred the sewage and reduce it to a slurry.  Sewage grinder pumps are capable of pumping this slurry through  smaller diameter pipe, as small as 1-1/4” and for much higher and longer distances than sewage handling pumps.

Jim Murray
Model #
Manufacturer Manufacturer
Model #
Switch HP RPM Volt PH FLA Cord Discharge   Shut Off   TDH 10' 30' 50' 60' 70' 75' 80' 85' 90' 100' 120' 140'
PZM-SGVF2022L Barnes  SGVF2022L  Manual   2   3450   240   1   15.0   15'   1-1/4"     101'    GPM  58   57   56   54   48   45   40   35   28   -   -   - 
PZM-SGVF2002L Barnes  SGVF2002L  Manual  2  3450  200  1  17.0  15'  1-1/4"    101'   GPM  58   57  56   54  48  45  40  35   28   2   -  -
PZM-OGP2022L Barnes  OGP2022L  Manual   2   3450   240   1   15.0   15'   1-1/4"     200'    GPM  29   29   29   29   29   29   29   29   29   29   29   27 
PLG-GP-M231-15 Little Giant GP-A231-15  Manual   2  3450   230  1  13.9   15'   1-1/4"    130'   GPM  33   32   31  30   28   26  25   24   22   20  10  -
PLG-GP-A231-20 Little Giant  GP-A231-20  Auto   2   3450   230   1   13.9   20'   1-1/4"     130'    GPM  33   32   31   30   28   26   25   24   22   20   10   - 
PLG-GP-A201-20 Little Giant  GP-A201-20  Auto   2   3450   208   1   13.9   20'   1-1/4"     130'    GPM  33   32   31   30   28   26   25   24   22   20   10   - 
ZBUR-SGVF2062L Barnes  SGVF2062L Manual   2   3450   200   3   11.0   15'   1-1/4"     101'    GPM  58  57   56   54  48  45   40   35   28   2    -  - 
ZBUR-SGVF2032L  Barnes  SGVF2032L Manual   2   3450   240   3  9.0   15'  1-1/4"     101'   GPM  58  57  56  54   48   45   40   35   28   2    -    - 
ZBUR-SGVF2042L  Barnes  SGVF2042L  Manual   2   3450  480  3  4.0  15'   1-1/4"     101'    GPM  58   57   56   54   48   45   40   35   28   2  -   - 

 

CUTTER PUMPS (Coming Soon)

                

Cutter pumps are very powerful sewage handling pumps that cut and  pass the solid.  Utilizing a Tungsten Carbide tipped impeller and a High Chrome Iron Cutter Plate, cutter pumps will solve the most demanding sewage and wastewater applications. As the solids pass through the cutter plate, they are cut into pieces and the deep vane impeller passes them along.

Jim Murray
Model #
Manufacturer Manufacturer
Model #
Switch HP RPM Volt PH FLA Cord Discharge   Shut Off   TDH 10' 30' 50' 60' 70' 75' 80' 85' 90' 100' 120' 140'
PZM-SGVF2022L Barnes  SGVF2022L  Manual   2   3450   240   1   15.0   15'   1-1/4"     101'    GPM  58   57   56   54   48   45   40   35   28   -   -   - 

 

BATTERY OPERATED PUMPS

         

Emergency back-up pumps for taking over during power or primary pump failure.

Jim Murray
Model #
Manufacturer Type/Model# HP RPM Volt PH FLA Cord Discharge   Shut Off   TDH 5' 8' 10' 12' 15' 17' 20'
PZM-DC2100  Metropolitan   12V Battery Back-Up   N/A   N/A   DC/12V   N/A   N/A   5'   1-1/4"     17'    GPM  24   18   14   10   4   -   - 
PGT-PHCC-2400   Glentronics   12V Battery Back-Up  N/A   N/A   DC/12V   N/A   N/A     1-1/2"     17'   GPM   52   45   42  32  12   -   - 
PJM-E-36  Jim Murray   12V Battery Back-Up   N/A   N/A   DC/12V   N/A   N/A   10'   1-1/4"     20'    GPM  45   40   35   21 16   11   - 
PVL-PKG-MAX-12V  Jim Murray   Primary Pump/PVL-ES-SFS   1/3   1550   115   1   10.0   10'   1-1/2"     20'    GPM  50   44   42   38   27   12   - 

 Metropolitan   12V Back-Up/ PZM-DC2100   N/A   N/A   DC/12V   N/A   N/A   5'   1-1/4"     17'    GPM  24 18  14   10  4  -   - 
PLG-PKG-MAX12V2  Jim Murray   Primary Pump/ PVL-ES-SFS  1/3  1550  115  1 10.0  10'  1-1/2"    20'   GPM  50  44  42  38  27 12  -
   Metropolitan   12V Back-UP/PZM-DC2100  N/A  N/A  DC/12V  N/A  N/A  5'  1-1/4"    17'   GPM  24  18  14  10  4  -  -
PLG-PKG-6CIA12V  Little Giant   Primary Pump/PLG-6-CIA   1/3   1550   115   1   9.0   10'   1-1/2"     18'    GPM  45   36   28   22   12   -   - 

 Metropolitan  12V Back-Up/PZM-DC2100  N/A   N/A   DC/12V   N/A   N/A   5'   1-1/4"     17 '    GPM  24   18  14   10   4    -   - 
PLG-PKG6CIA12V2    Little Giant   Primary Pump/PLG-6-CIA      1/3  1550   115  1  9..0  10' 1-1/2"     18'   GPM  45  36  28  22  12  -   -
   Metropolitan   12V Back-Up/PZM-DC2100 N/A N/A  DC/12V N/A N/A  5' 1-1/4"     17'   GPM   24  18  14  10  4  -  -
PGT-PS-C33   Glentronics   Primary Pump/ PGT-S3033  1/3  3450   115  1  4.0   20'  1-1/2"     30'    GPM  -   -   50   -    -  -  -
   Glentronics  12V Back-Up/PGT-PHCC-2400  N/A  N/A  DC/12V  N/A   N/A   1-1/2"     17'    GPM 52  45  42   32 12   -  -
PZM-SUMPRO-75NB  Metropolitan   AC/DC Converter   N/A   N/A  120      15      "         GPM

 -  

 -  

 -   -  -    -   - 
PZM-STORMPRO-11  Metropolitan   AC/DC Single Pump System   1/3   3600   AC / DC   1   4.5   10'   1-1/2"     25'    GPM  58   53   48   42   37   28   22 
PZM-STORMPRO-55  Metropolitan   AC/DC Dual Pump System   1/2   3600   AC / DC   1   5.8   10'   1-1/2"     30'    GPM  80   73   68   65   55   44  38 
PZM-GOLD33-10  Metropolitan   AC/DC Single Pump System   1/3   3600   AC / DC   1   4.5   10'   1-1/2"     25'    GPM  58   53   48   42   37   28   22 
PZM-GOLD50-10  Metropolitan   AC/DC Single Pump System   1/2   3600   AC / DC   1   5.8   10'   1-1/2"     30'    GPM  80   73   68   65   55   44   38 
PZM-GOLD75-10  Metropolitan   AC/DC Single Pump System   3/4   3600   AC / DC   1   7.5   15'   1-1/2"     35'    GPM  92   86   82   78   70   60   55 
PZM-GOLD33-55  Metropolitan   AC/DC Dual Pump System   1/3   3600   AC / DC   1   4.5   10'   1-1/2"     25'    GPM  58   53   48   42   37   28   22 
PZM-GOLD50-55  Metropolitan   AC/DC Dual Pump System   1/2   3600   AC / DC   1   5.8   10'   1-1/2"     30'    GPM  80   73   68   65   55   44   38 
PZM-GOLD75-55  Metropolitan   AC/DC Dual Pump System   3/4   3600   AC / DC   1   7.5   15'   1-1/2"     35'    GPM  92   86   82   78   70   60   55 
PZM-PUMPGUARD  Metropolitan   Back-up Switch & Alarm   N/A   N/A    120    N/A                                      
SRB-ULTRANATOR     SJE Rhombus   Duplex Alternating Control & Alarm  N/A   N/A   120   N/A                            
AZP-BATTERY-SL  Swid Sales  Maintenance Free Battery   N/A   N/A    12V    N/A                                      

 

HI-TEMP AND UTILITY PUMPS

                     

High temp pumps are used for pumping liquid/effluent with temperatures up to 200 degree Fahrenheit.

Jim Murray
Model #
Manufacturer Manufacturer
Model #
Switch HP RPM Volt PH FLA Cord Discharge   Shut Off   TDH 5' 8' 10' 12' 15' 18' 20' 25' 30' 35' 40' 45' 50'
PLG-HT6E-CIM-A Little Giant  HT-6E-CIA-FS  Auto   1/3   1550   115   1   10.1   15'   1-1/2"     16'    GPM  46   42   37   32   17   -   -   -   -   -   -   -   - 
PLG-HT10E-CIM-A Little Giant  HT-10E-CIA-FS  Auto   1/2   1550   115   1   10.5   15'   1-1/2"     22'    GPM  74   70   66   62   50   32   -   -   -   -   -   -   - 
PLG-5-MSP Little Giant  5-MSP  Manual   1/6   1150   115   1   5.0   10'   1"     26'    GPM  19   17   16   15   14   13   11   7   -   -   -   -   - 
PZM-LB-480        

Tsurumi

LB-480 Manual  2/3  3600  115   1  6.1  32'   2"     40'   GPM  62  58  53  55  50  45  42  32  22  11  -  -   -

PZM-LB-800

Tsurumi

LB-800

Manual  1.0    115    1  11.5  50'   2"     60'   GPM  82  80  78  76  73  68  66  60  52  47  38  27  18
PZM-UT70 Barnes  UT70  Manual   7/10   3450   115   1   8.0   50'   2"     38'    GPM  82   82   82   82   75   70   64   48   30   10   -   -   - 
PZM-UT125 Barnes  UT125  Manual   1.25   3450   115   1   15.0   50'   2"     50'    GPM  108   108   108   104   102   98   95   85   74   60   48   25   - 

 

SINK TRAY UNITS

          

These units sit on the floor or under cabinets, no need to dig a sump.  And are used for removing water/effluent from laundry sinks, bar sinks, laundry sinks, utility sinks, dehumidifiers and condensate.  Units are pre-assembled and ready to install. 

Jim Murray
Model #
Manufacturer Type/Model# HP RPM Volt PH FLA Cord Discharge   Shut Off   TDH 5' 8' 10' 12' 15' 18' 20' 25' 30'
PVL-WATERBOX-01  Jim Murray   PVL-WATERBOX-01 1/3  1550 115  1  6.0  10'   1-1/2"     20'   GPM  50  46  42  37 27 13 - - -
PVL-WATERBOX-02  Jim Murray   PVL-WATERBOX-02  1/3  3450  115  1  5.8  10'   1-1/2"     30'   GPM  50  47  43  39  34 27 24 20 13
PLG-WRS-6  Little Giant   WRS-6   1/3   1550   115   1   9.0   8'   1-1/2"     18'    GPM  46   32   29   22   12   -   -   -   - 
PLG-WRSC-6  Little Giant   WRSC-6   1/3   1550   115   1   9.0   8'   1-1/2"     18'    GPM  46   32   29   22   12   -   -   -   -